Basement central
Panel Specifications
Section titled “Panel Specifications”- Model: Harju/Famatel 3-rail IP65 (Motonet 90-01794)
- Feed: 4mm² 5-wire from main central
- Capacity: 3×20A (limited by feed wire)
- Main breaker: 63A 4P (TODO: Replace with 3×20A to match feed)
- RCCB protection: 2× 40A/30mA 4-pole
- Circuit positions: 42 (14 per phase, using hexadecimal: B1-11 to B1-1E per rail)
- Spare capacity: 10 additional modules
Circuit Distribution
Section titled “Circuit Distribution”RCCB 1 (40A/30mA)
Section titled “RCCB 1 (40A/30mA)”Protects general-use circuits on phases 1 and 2:
- Wall sockets (zones 1 & 2)
- Network cabinet
- Dehumidifier
RCCB 2 (40A/30mA)
Section titled “RCCB 2 (40A/30mA)”Protects specialized circuits on phases 2 and 3:
- Dishwasher (future)
- Manifold cabinet (Kincony)
- Workshop sockets
RCCB Bypass Circuits
Section titled “RCCB Bypass Circuits”Critical loads that bypass RCCB to prevent nuisance tripping:
- Heat pump (3-phase: B1-11, B1-21, B1-31)
- Basement lighting (B1-12)
- Ventilation (B1-33)
Load Planning
Section titled “Load Planning”Total basement area: 40m²
Permanent loads:
- Heat pump: 3×16A (3-phase)
- Dehumidifier: 330W (~1.5A)
- Network cabinet: Router, PoE switch, AP, NAS (~2A)
- Manifold cabinet: Kincony A4/A6 controller
- Ventilation: Variable speed fan
Intermittent loads:
- Power tools (workshop)
- Dishwasher (future)
Circuits
Section titled “Circuits”| Code | Description | Location | RCCB | Fuse | Phase | TODO |
|---|---|---|---|---|---|---|
| B1-11 | Heat pump - Phase 1 | Basement | no | 16A | 1 | |
| B1-12 | Basement lighting | Basement | no | 10A | 1 | |
| B1-13 | Wall sockets | Basement - Zone 1 | yes | 16A | 1 | |
| B1-14 | Network cabinet | Basement | yes | 10A | 1 | |
| B1-15 | Dehumidifier | Basement | yes | 10A | 1 | |
| B1-16 | unwired | - | no | - | 1 | |
| B1-17 | unwired | - | no | - | 1 | |
| B1-18 | unwired | - | no | - | 1 | |
| B1-19 | unwired | - | no | - | 1 | |
| B1-1A | unwired | - | no | - | 1 | |
| B1-1B | unwired | - | no | - | 1 | |
| B1-1C | unwired | - | no | - | 1 | |
| B1-1D | unwired | - | no | - | 1 | |
| B1-1E | unwired | - | no | - | 1 | |
| B1-21 | Heat pump - Phase 2 | Basement | no | 16A | 2 | |
| B1-22 | Wall sockets | Basement - Zone 2 | yes | 16A | 2 | |
| B1-23 | Dishwasher (future) | Basement | yes | 16A | 2 | Install if needed |
| B1-24 | Manifold cabinet (Kincony A4/A6) | Basement - Manifold cabinet | yes | 10A | 2 | |
| B1-25 | unwired | - | no | - | 2 | |
| B1-26 | unwired | - | no | - | 2 | |
| B1-27 | unwired | - | no | - | 2 | |
| B1-28 | unwired | - | no | - | 2 | |
| B1-29 | unwired | - | no | - | 2 | |
| B1-2A | unwired | - | no | - | 2 | |
| B1-2B | unwired | - | no | - | 2 | |
| B1-2C | unwired | - | no | - | 2 | |
| B1-2D | unwired | - | no | - | 2 | |
| B1-2E | unwired | - | no | - | 2 | |
| B1-31 | Heat pump - Phase 3 | Basement | no | 16A | 3 | |
| B1-32 | Workshop sockets | Basement - Workshop area | yes | 16A | 3 | |
| B1-33 | Ventilation | Basement | no | 10A | 3 | |
| B1-34 | unwired | - | no | - | 3 | |
| B1-35 | unwired | - | no | - | 3 | |
| B1-36 | unwired | - | no | - | 3 | |
| B1-37 | unwired | - | no | - | 3 | |
| B1-38 | unwired | - | no | - | 3 | |
| B1-39 | unwired | - | no | - | 3 | |
| B1-3A | unwired | - | no | - | 3 | |
| B1-3B | unwired | - | no | - | 3 | |
| B1-3C | unwired | - | no | - | 3 | |
| B1-3D | unwired | - | no | - | 3 | |
| B1-3E | unwired | - | no | - | 3 |